Product Introduction
NFIN Residual Current Device
Application
The Residual Current Device NFIN is in conformity with the standard of IEC61008. It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth leakage.
NFIN RCD is mainly suitable for using in varieties of plants, enterprises, buildings, constructions, commerce, guesthouses and families. It can be used in circuits of 1 phase 230V and 3 phase 400V 50/60Hz.
Specifications
Number of Poles
|
2P, 4P
|
Rated Current (A)
|
16, 20, 25, 32, 40, 50, 63, 80, 100
|
Rated Residual Operating Current (IΔn)(mA)
|
30, 100, 300, 500
|
Rated Residual Non-operation Current (IΔno)(mA)
|
≤0.5IΔn
|
Rated Voltage (V)
|
AC 230/400
|
Residual Current Off-time
|
≤0.1S
|
Short Circuit Capacity (Icu)
|
3000A
|
Endurance
|
≥4000
|
Protection Degree
|
IP20
|
Normal Operation and Mounting Requirement
● Circumstance temperature -5°C~+40°C, average temperature not exceeding 35°C.
● Altitude above sea level less than 2000m.
● Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
● Installation class II or III.
● Pollution class II.
● Installation method DIN Rail mounting type.
● The external magnetism shall not be more than 5 times of terrestrial one.
● Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position.
Operation Principle
Overall And Mounting Dimensions (Unit: mm)