Product Catalogue
Home > Product Center - CNKNGLI->Moulded case circuit breaker -> KLM3 Series Moulded Case Circuit Breaker
Product Information Return to the upper
Product Introduction
Application
KLM3 series moulded case circuit breaker , it’s applicable circuit of AC 50Hz(or 60Hz),rated insulation voltage 690V(AM3-125 500V),rated operating voltage AC 690V or below ,rated operating current 12.5-1600A, for distribute energy of electric and infrequent making and breaking circuit in normal condition. The circuit-breakers are provided with the function of the protection against overload and short circuit and under-voltage. The circuit breakers comply with standard of IEC60947-2. The circuit-breakers are double insulating (Inm=250A or above), the control circuit of the accessories is set apart with the main circuit , and doesn’t need to open the cover of the circuit-breaker when install the accessories.

Specifications(Table 1)
Type Pole
number
Rated
insulating
voltage
(V)
Rated
operating
voltage
(V)
Ultimate short circuit
breaking capacity Icu(KA)
Rated shortcircuit serrice
breaking capocity Ics(%icu)
Utilization
category
AC380V(400) AC660V(690)
KLM3-125L 1,2,3,4 500 500 25 - 50% A
KLM3-160L 3, 4 690 690
and
below
35 8 75%
KLM3-160M 50 10 75%
KLM3-250L 800 35 14 100%
KLM3-250M 65 18 75%
KLM3-250H 85 20 75%
KLM3-400L 35 18 100%
KLM3-400M 65 22 100%
KLM3-400H 100 30 75%
KLM3-630L 35 20 100%
KLM3-630M 50 22 100%
KLM3-630H 65 25 100%
KLM3-800L 35 20 100%
KLM3-800M 50 22 100%
KLM3-800H 65 25 100%
KLM3-1250/1600L 3 50 20 100%

Trip units main technical parameter (see table 2)

Table 2
Type Thermal magnetic release Electronic release
Rated current In(A) Note Rated current In(A) Note
KLM3-125 12.5,16,20,25,32,40,
50,63,80,100,125
T fixed
M fixed
-  
KLM3-160 16,20,25,32,40,50,
63,80,100,125,160
T adjustable (0.7~1In)
M fixed
-  
KLM3-250 100,125,160,180,
225,250
T adjustable (0.7~1In)
M fixed
-  
KLM3-400 225,250,315,
350,400
T fixed or
adjustable (0.7~1In)
M fixed
320,400 I1=0.4…1×In KLM3 PR211(L-LI)
I1=0.4…1×In KLM3 PR212(LSI-LSIG)
Tripping between 1.05…1.3×I1
(IEC60947-2) I2t=constant
(Long-time overload protection)
I2=1-2-3-4-6-8-10×In
t2=0.05s,0.1s,0.25s,0.5s adjustable
(Short-circuit short time delay protection)
I3=1.5-2-4-6-8-10-12×In
(Instantaneous short-circuit protection)
I4=0.2-0.3-0.4-0.6-0.8-0.9-1×In
t4=0.1s,0.2s,0.4s,0.8s adjustable
(Earth fault protection)
KLM3-630 400,500,630 T fixed
M fixed
630
KLM3-800 630,700,800 T fixed
M fixed
800
KLM3-1250 - - 800,1000,
1250
KLM3-1600 - - 1000,
1250,1600
Note: T-thermal M-magnetic L-long time S-short time relay I-instantaneous G-earth fault KLM3-125/160 In=12.5,16,20,32,40 magnetic protection that is fixed at 500A.

Accessories
1. The external accessories of the breaker
■ Motor-driven operation device
1) Wiring diagram of type CDM electromagnetic operation device(fitting KLM3-125, 160,250) see the following drawing (wiring diagram of the external accessories of the breaker in the dotted frame).

Code description: SB1、SB2 stand for push button.(provided by users themselves)
Number “1”、“2”、“3” stand for number of wiring terminals.
Voltage rating: AC50Hz 230V、400V, DC 220V
2) Wiring diagram of type CD motor-driven operation device (fitting KLM3-400、630、800) see belows (wiring diagram of the external accessories of the breaker in the dotted frame)

Online Order:
Order Product: * Number: *
Contact: * Telephone: *
Company Name: E-mail: *
Address:
Country/Region:
Node:
 
收缩
  • 咨询服务热线

  • 0577-62868266